AC Voltage Ranges |
400.0mV, 4.000V, 40.00V, 400.0V, 600V |
|
AC Voltage Accuracy (4V to 400V range) |
±(1.5% of Rdg + 4
digits) (50 to 500Hz) |
|
|
|
AC Current Ranges |
400.0A, 800A |
|
AC Current Accuracy (0 to 600A range) |
±(1.5% of Rdg + 5
digits) (40 to 100Hz) |
|
|
|
DC Voltage Ranges |
400.0mV, 4.000V, 40.00V, 400.0V, 600V |
|
DC Voltage Accuracy (4V to 400V ranges) |
±(0.5% of Rdg + 3
digits) |
|
|
|
DC Current Ranges |
400.0A, 1000A |
|
DC Current Accuracy (0 to 800A range) |
±(1.5% of Rdg + 4
digits) |
|
|
|
Resistance Ranges |
400.0Ω, 4.000Ω, 40.00Ω,
400.0kΩ, 40.00MΩ |
|
Resistance Accuracy (4 to 400kΩ
range) |
±(0.6% of Rdg + 4
digits) |
|
|
|
Capacitance Ranges |
500.0nF, 5.000µF,
50.00µF, 500.0µF,
3000µF |
|
Capacitance Accuracy |
±(3.5% of Rdg + 6
digits) |
| |
|
General Specifications |
|
Display |
3-3/4 digits 4000-count LCD display |
|
Refresh Rate |
3 per second nominal |
|
Polarity |
Automatic |
|
Low Battery |
Below 2.4 volts approx. |
|
Operating Temperature |
0°C to 40°C |
|
Relative Humidity |
Max R.H. 80% for temperature up to 31°C
decreasing |
|
linearly to 50% R.H. at 40°C |
|
Storage Temperature |
-20°C to 60°C,
<80% R.H. (with battery removed) |
|
Temperature Coefficient |
Nominal 0.15 x (specified accuracy)/°C
at |
|
(0°C to 18°C
or 28°C to 40°C),
or otherwise specified |
|
Sensing |
True RMS |
|
Safety |
Meets EN61010-1: 2001; IEC61010-2-032 (2002),
|
|
EN61010-2-032 (2002), UL61010B-2-032 (2003), |
|
CAT III 600 Volts AC/DC |
|
Transient Protection |
6.5kV (1.2/50µs
surge) |
|
Pollution Degree |
2 |
|
EMC |
Meets EN61326-1 |
|
Power Supply |
Two 1.5V size 'AAA' (NEDA 24G or IEC R03)
batteries |
|
Power Consumption |
Typical 11mA for AC amps/DC amps and 2.9mA all |
|
other functions |
|
Jaw opening/Conductor size |
50mm maximum |
|
Size |
227mm (L) x 78mm (W) x 40mm (D) |
|
Weight |
290g approx. |
| |
|
Included
Accessories |
|
Test Leads,
Batteries (installed), Users Manual, and
Carrying Case. |