The AMB-6D's full suite of features
translate into robust functionality, durable and dependable
Benefits:
- Ideal for checking motor windings and cable insulation.
- Fast and easy to use.
- Warns against hazardous energized systems.
- Designed for use in remote locations.
- Software provided for printing reports.
- All accessories and software are included with product.
|
|
 |
Features
- Tests insulation of wires, cables, transformers and electrical
motors.
- Comes as a complete kit including test leads and PC software.
- Selectable test voltages up to 1000V.
- Programmable timer to perform the Dielectric Absorption Ratio
Test.
- Sensitive Ohmmeter for checking resistance of motor windings.
- Selectable polarization of ohmmeter for checking grounding
continuity.
- Automatic voltmeter warns against hazardous energized systems.
- Fast and easy to use, rugged durable design.
- Internal memory to store measurements for future reference.
- Data download to PC.
- Battery operated.
 |
|
|
|
|
Specifications |
|
Continuity |
|
Test Mode |
Measuring Range |
Resolution
|
Accuracy |
|
AUTO, R+, R |
0.01Ω
to 19.99Ω |
0.01Ω |
±(2% of Rdg + 2 digits) |
| 20.0Ω to
99.9Ω |
0.1Ω |
|
R +Timer
R -Timer |
0.01Ω
to 9.99Ω |
0.01Ω |
±(2% of Rdg + 2 digits) |
|
| |
|
Test Current: |
>200mA DC up to 16Ω
(includes the resistance of the calibration) |
|
40mA DC from 16Ω
to 99.9Ω |
|
Test Current Resolution: |
1mA |
|
Open Circuit Test Voltage |
9V |
|
| |
|
Insulation Resistance |
|
Test Voltage |
Measuring Range (MΩ) |
Resolution
|
Accuracy |
|
50V |
0.01MΩ
to 19.99MΩ |
0.01Ω |
±(2% of Rdg + 2 digits) |
| 20.0MΩ
to 49.9MΩ |
0.1Ω |
±(5% of Rdg + 2 digits) |
| 50.0MΩ
to 99.9MΩ |
0.1Ω |
±(5% of Rdg + 2 digits) |
|
100V |
0.01MΩ
to 19.99MΩ |
0.01Ω |
±(2% of Rdg + 2 digits) |
| 20.0MΩ
to 99.9MΩ |
0.1Ω |
±(2% of Rdg + 2 digits) |
| 100.0MΩ
to 199.9MΩ |
0.1Ω |
±(5% of Rdg + 2 digits) |
|
250V |
0.01MΩ
to 19.99MΩ |
0.01Ω |
±(2% of Rdg + 2 digits) |
| 20.0MΩ
to 199.9MΩ |
0.1Ω |
±(2% of Rdg + 2 digits) |
| 200MΩ to
249MΩ |
1Ω |
±(2% of Rdg + 2 digits) |
| 250MΩ to
499MΩ |
1Ω |
±(5% of Rdg + 2 digits) |
|
500V |
0.01MΩ
to 19.99MΩ |
0.01Ω |
±(2% of Rdg + 2 digits) |
| 20.0MΩ
to 199.9MΩ |
0.1Ω |
±(2% of Rdg + 2 digits) |
| 200MΩ to
499MΩ |
1Ω |
±(2% of Rdg + 2 digits) |
| 500MΩ to
999MΩ |
1Ω |
±(5% of Rdg + 2 digits) |
|
1000V |
0.01MΩ
to 19.99MΩ |
0.01Ω |
±(2% of Rdg + 2 digits) |
| 20.0MΩ
to 199.9MΩ |
0.1Ω |
±(2% of Rdg + 2 digits) |
| 200MΩ to
999MΩ |
1Ω |
±(2% of Rdg + 2 digits) |
| 1000MΩ
to 1999MΩ |
1Ω |
±(5% of Rdg + 2 digits) |
|
| |
|
Automatic selection of the measuring
range |
|
Open Circuit Voltage: |
1.1 x Rated voltage test |
|
Short Circuit Current: |
<3.0mA to 500V |
|
<2.0mA to 50V, 100V, 250V, 1000V |
|
Rated Measurement Current: |
2.17mA to 500V/230kΩ |
|
1.0mA to 1000V/1MΩ |
|
|
If the instrument measures a voltage
higher than 30V, the instrument will not take a measurement. |
|
|
|
General Specifications (23°C
±5°C <70% R.H.) |
|
Display: |
Custom LCD |
|
Memory: |
350 tests |
|
Interface: |
Optical RS-232 to print or download
the tests |
| |
|
Environmental |
|
Operating Temperature: |
-10°C to
50°C (14°F
to 140°F) <80% R.H. |
|
Storage Temperature: |
-20°C to
60°C (68°F
to 140°F) <70% R.H. |
| |
|
EMC |
|
Radiated Emissions: |
EN 55011 |
|
Immunity: |
EN 50140, EN 61000 |
|
Electrostatic Discharge: |
EN 61000-4-2 |
|
R.F. Field: |
EN 50140 |
|
Fast Transient: |
EN 61000-4-4 |
|
|
|
Safety |
|
Insulation: |
Class 2, double insulated |
|
Over-voltage Category: |
CAT III, 300V |
|
|
|
Mechanical |
|
Dimensions: |
222mm (L) x 162mm (W) x 57mm (D) |
|
8.8" (L) x 6.4" (W) x 2.25" (D) |
|
Weight: |
1000gms (2.2lb) |
|
Battery Supply: |
6ea. 1.5V type 'AA' batteries |
|
Automatic Turn Off: |
Turns off after 5 minutes without use |
|
|
|
|
Included
Accessories |
|
Test Leads (complete set with cables,
alligator clip and probes), Serial cable, software, and user's
manual. |
|