Ground Resistance (Auto
Range): |
|
Range |
Resolution |
Accuracy |
|
0.025Ω to
0.250Ω |
0.002Ω |
±1.5% ±0.05Ω |
|
0.250Ω to
1.000Ω |
0.02Ω |
±1.5% ±0.05Ω |
|
1.001Ω to
9.999Ω |
0.02Ω |
±1.5% ±0.1Ω |
|
10.00Ω to
50.00Ω |
0.04Ω |
±2.0% ±0.3Ω |
|
10.01Ω to
99.99Ω |
0.04Ω |
±2.0% ±0.5Ω |
|
100.0Ω to
200.0Ω |
0.4Ω |
±3.0% ±1.0Ω |
|
200.1Ω to
400.0Ω |
2Ω |
±5.0% ±5Ω |
|
400.0Ω to
600.0Ω |
5Ω |
±10% ±10Ω |
|
600.1Ω to
1500Ω |
20Ω |
±20%
|
|
| |
|
High and Low Alarm: |
|
Range |
Range |
Resolution |
|
High Alarm |
0Ω to
1510Ω |
1Ω |
|
Low Alarm |
0Ω to
1510Ω |
1Ω |
|
| |
|
Ground Leakage Current
(Auto Range, 50/60Hz, True-rms, Crest Factor <3.0) |
|
Range |
Resolution |
Accuracy |
|
0.200mA to 1.000mA |
0.001mA |
±2.0%
±0.05mA |
|
1.00mA to 10.00mA |
0.01mA |
±2.0%
±0.03mA |
|
10.0mA to 100.0mA |
0.1mA |
±2.0% ±0.3mA |
|
100mA to 1000mA |
1mA |
±2.0% ±3mA |
|
0.200A to 4.000A |
0.001A |
±2.0%
±0.03mA |
|
4.00A to 30.00A |
0.01A |
±3.0%
±0.03mA |
|
| |
|
Accuracy of Resistance Calibration
Plate: ±0.5% |
|
Data Logging Capacity: 116 Records |
|
Data Logging Interval: 1 to 255 seconds |
|
|
|
General Specifications |
|
|
|
Conductor Size |
23mm (0.9") approx. |
|
Display |
4-digits (9999-counts) LCD |
|
Sampling Time |
0.5 seconds |
|
Range Selection |
Auto |
|
Overload Indication |
"OL" |
|
Low Battery Indication |
Yes |
|
Power Supply |
9 volt IEC 6 LR61 (Alkaline)
battery |
|
Battery Life |
3000 measurements |
|
Operating Temperature |
0°C to 50°C
<85% R.H. (non-condensing) |
|
Storage Temperature |
0°C to 60°C
<75% R.H. (non-condensing) |
|
Dimensions |
257mm (L) x 100mm (W) x 47mm (D) |
|
Weight |
640gms |
|
|
|
|
|
Included
Accessories |
|
Resistance Calibration Plate, 9V
battery, User's manual |
|