Rapid-Tech Equipment Logo Combo Kit Power Quality Recorder Power Quality Analyzer Multifunction Digital Multimeter

Nationwide - Call 1800 358 531 

Amprobe logo

HD160C Heavy Duty Multimeter

 

The HD160C is designed for professional use in harsh environments. The meter is unusually rugged and reliable in everyday heavy use applications. The meter is made using waterproof construction to prevent dirt, grime and moisture from entering the case and causing inaccurate readings or damaging shorts. Built of tough, fire-retardant thermoplastic resistant to grease and chemical spills, with all sensitive components shock-mounted for a drop resistance to at least eight feet.

Model HD160C has an extended voltage measurement capability of 1500 V dc and 1000 V ac, unmatched by any other line of digital multimeters. The extended voltage ranges can withstand transients up to 12 kV.
 

HD160C Heavy Duty Multimeter

 

 

Rugged DMMs constructed for IP67 water proofing and harsh environments

Features

  • Highest voltage capability, measuring to 1500 Vdc and 1000 Vac
  • CAT IV 1000 V rated
  • Special sealing for environment and water resistance. IP67 rated
  • Constructed with drop-resistant housing and PCB mounting
  • Measures capacitance, temperature and frequency
  • Superior 10,000 count resolution with bar graph
  • Magne-Grip™ holster, frees both hands for work
  • Includes high voltage test leads with threaded alligator clips
  • Temperature measurement built-in
  • Frequency and capacitance
  • Digi-Glo™ bright backlight
  • Display 4 digit LCD, 9999 counts, with annunciators, menu features and 41 segment bargraph.
  • Polarity Indication Automatic
  • Input overload indication OL, -OL.
  • Auto Power-Down

Safety Conformity

Specifications

DC Voltage Ranges

1000mV, 10V, 100V, 1500V

DC Voltage Resolution

0.1mV in 1000mV range

DC Voltage Accuracy

±(0.1% of Rdg + 5 digits)

DC Voltage Input Impedance

10MΩ

 

 

DC Current Ranges

100μA, 100A, 10mA, 100mA, 400mA, 2A

DC Current Resolution

0.1μA in 100μA range

DC Current Accuracy

±(0.5% of Rdg + 5 digits) 1000μA to 400mA range

±(1.5% of Rdg + 10 digits) 2A range

 

 

AC Voltage True RMS Ranges

1000mV, 10V, 100V, 1000V

AC Voltage Resolution

0.1mV in 1000mV range

AC Voltage Accuracy  (45Hz to 400Hz)

±(1.2% of Rdg + 10 digits) 100mV range

AC Voltage Accuracy  (45Hz to 500Hz)

±(1.2% of Rdg + 10 digits) 10V, 100V ranges

AC Voltage Accuracy  (500Hz to 2kHz)

±(2.0% of Rdg + 10 digits) 10V, 100V ranges

AC Voltage Accuracy  (45Hz to 1kHz)

±(2.0% of Rdg + 10 digits) 1000V range

AC Voltage Input Impedance

10MΩ

Conversion Type

True rms, AC couplet 5% to 100% range

Crest Factor

≤3

 

 

AC Current True RMS Ranges

100μA, 100A, 10mA, 100mA, 400mA, 2A

AC Current Resolution

0.1μA in 100μA range

AC Current Accuracy (45Hz to 1kHz)

±(1.5% of Rdg + 10 digits) 100μA to 100mA range

±(2.0% of Rdg + 10 digits) 400mA range

±(2.0% of Rdg + 20 digits) 2A range

Conversion Type

True rms, AC couplet 5% to 100% range

Crest Factor

≤3

 

 

Resistance Ranges

1000Ω, 10kΩ, 100kΩ, 1000kΩ, 10MΩ, 40MΩ

Resolution

0.1Ω 1000Ω range

Resistance Accuracy

±(0.5% of Rdg + 8 digits) 1000Ω to 1000kΩ range

±(1.0% of Rdg + 10 digits) 10MΩ range

±(2.0% of Rdg + 10 digits) 40MΩ range

 

 

Capacitance (Auto/Manual Ranging)

40nF, 400nF, 4μF, 40μF, 400μF (3999 counts)

Resolution

30.01nF

Accuracy 

±(3.0% of Rdg + 10 digits) 40nF, 400μF ranges

±(3.0% of Rdg + 5 digits) 400nF, 40μF ranges

Test Voltage

<1V

 

 

Temperature Ranges

-20°C to 1300°C (-4°F to 2372°F) 3999-counts

Accuracy

±(2.0% of Rdg + 4°C) -20°C to 10°C range

±(1.0% of Rdg + 3°C)  10°C to 200°C range

±(2.0% of Rdg + 2°C)  200°C to 1300°C range

±(2.0% of Rdg + 8°C) -4°F to 50°F range

±(1.0% of Rdg + 6°C)  50°F to 400°F range

±(2.0% of Rdg + 4°C)  400°F to 2372°F range

 

 

Continuity Audible Test Indication

<40Ω

Response Time

<100msec

   

General Specifications

Display
 

4 digit LCD, 9999-counts, with annunciators & menu features and 41 segment Bar-Graph

Display Refresh Rate

2.5/sec, nominal, 20/sec for bar-graph

Polarity Indication

Automatic

Input Overload Indication

Yes

Low Battery Indication

Yes (<50 hours battery life remain, accuracy no longer guaranteed

Operating Temperature

0°C to +50°C (<75% R.H.)

Storage Temperature

-20°C to +60°C (0 to 80% R.H.) battery removed

Fuse

F2A/1500V fuse (8mm x 65mm), I.R. 30kA

Power Supply

Std 9V battery, NEDA 1604, JIS 006P, IEC 6F22

Auto Power Down

Meter powers down after 30 minutes approx. of inactivity

Dimensions 

200mm (H) x 102mm (W) x 59mm (D)

7.9" (H) x 4.0" (W) x 2.3" (D)

Weight

642g (20oz) incl battery

Case Material

Flame retardant, high-impact thermoplastic

Safety 

Meets EN 61010-1 CAT IV 1000V (1500V DC max),

Class II, EN60529:IP67

EMC

Meets EN 61326-1

 

Included Accessories

Included Accessories

Heavy Duty CAT IV 1000V Test leads with threaded Alligator clips, Batteries (installed), Hex wrench in holster, Holster with Magne-Grip flex strap,  K-type Thermocouple, Temperature Adaptor and User manual.


Fluke | Hart | Reed | Yokogawa | EuroSMC | Kyoritsu | Megger | | Tenmars | Tektronix | Amprobe | CIE | Silvertronic |
 Site Map | Search | About Us | Contact Us

 

Rapid-Tech Equipment
ABN 79 883 184 102
1300 Ferntree Gully Road. Scoresby. Victoria 3179
P.O. Box 4243 Knox City Centre. Victoria 3152

Phone: +61 3 9763 3299     Fax: +61 3 9753 2132