Rapid-Tech Equipment Logo Combo Kit Power Quality Recorder Power Quality Analyzer Multifunction Digital Multimeter

Nationwide - Call 1800 358 531 

 Fluke Test Instruments Logo

Models 1550C and 1555 10kV Insulation Tester - Specifications
 

Electrical Specifications
The tester's accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ±.25% per °C, except on the 20% bands add ±1% per °C.

 

Insulation Resistance Measurement

Test Voltage (DC)

Range (DC)

Accuracy

250 Volts

< 200kΩ
200kΩ to 5GΩ
5GΩ to 50GΩ
> 50GΩ

unspecified
±5% of rdg
±20% of rdg
unspecified

500 Volts

< 200kΩ
200kΩ to 10GΩ
10GΩ to 100GΩ
> 100GΩ

unspecified
±5% of rdg
±20% of rdg
unspecified

1000 Volts

< 200kΩ
200kΩ to 20GΩ
20GΩ to 200GΩ
> 200GΩ

unspecified
±5% of rdg
±20% of rdg
unspecified

2500 Volts

< 200kΩ
200kΩ to 50GΩ
50GΩ to 500GΩ
> 500GΩ

unspecified
±5% of rdg
±20% of rdg
unspecified

5000 Volts

< 200kΩ
200kΩ to 100GΩ
100GΩ to 1TΩ
> 1TΩ

unspecified
±5% of rdg
±20% of rdg
unspecified

10000 Volts

< 200kΩ
200kΩ to 200GΩ
10GΩ to 2TΩ
> 2TΩ

unspecified
±5% of rdg
±20% of rdg
unspecified

 
 

Bar Graph Range

0 to 1TΩ

Insulation Test Voltage Accuracy

-0%, +10% at 1mA load current

Induced AC Mains Current Rejection

2mA maximum

Charging Rate for Capacitance Load

5 seconds/µF

Discharge Rate for Capacitance Load

1.5 seconds/µF

 
 

Measurement

Range

Accuracy

Leakage Current

1nA to 2mA

±(5% of rdg + 2nA)

Capacitance

0.01µF to 15.00µF

±(15% of rdg + 0.03µF)

Live Circuit Warning

30 Volts to 660 Volts AC/DC 50/60Hz

±(15% of rdg + 2V)

 
 

Measurement

Range

Resolution

Timer

0 to 99 minutes

setting: 1 minute
Indication: 1 second

 
 

General Specifications

Display

75mm x 105mm

Power Supply

12 Volt lead-acid rechargeable battery, (Yuasa NP2.8-12)

Charger Unit



 

85 Volts to 250 Volts 50/60 Hz 20VA
Note: this Class II (double insulated) instrument is supplied with Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.

Operating Temperature

-20°C to 50°C (-4°F to 122°F)

Storage Temperature

-20°C to 65°C (-4°F to 149°F)

Humidity

80% to 31°C decreasing linearly to 50% at 50°C

Altitude

2000 meters

Enclosure Sealing

IP40

Overload Protection (Input)

1000 Volts AC

Electromagnetic Compatibility

EN 61326

Safety Compliance

EN 61010, EN 61557 Parts 1 and 2, IEC 61010-1,
CAT III 1000V, CAT IV 600V

Pollution Degree

2

Dimensions

170mm (H) x 242mm (W) x 330mm (L)
6.7" (H) x 9.5" (W) x 13" (L)

Weight

3.6kg (7.94lb)

Certifications

Fluke 1555 Certifications

 


Fluke | Hart | Reed | Yokogawa | EuroSMC | Kyoritsu | Megger | | Tenmars | Tektronix | Amprobe | CIE | Silvertronic |
 Site Map | Search | About Us | Contact Us

 

Rapid-Tech Equipment
ABN 79 883 184 102
1300 Ferntree Gully Road. Scoresby. Victoria 3179
P.O. Box 4243 Knox City Centre. Victoria 3152

Phone: +61 3 9763 3299     Fax: +61 3 9753 2132