Rapid-Tech Equipment Logo Combo Kit Power Quality Recorder Power Quality Analyzer Multifunction Digital Multimeter

Nationwide - Call 1800 358 531 

 Fluke Test Instruments Logo

1740 Series 3-Phase Power Quality Logger - Specifications

 

General Specifications

Intrinsic Error

Refers to the reference conditions and is guaranteed for two years.

Warranty

Two years

Recalibration Interval

Two years recommended

Quality System
 

Developed, designed, and manufactured according to DIN ISO 9001.

Reference Conditions




 

 

23°C 2K; 74°F ±2K, Vm=230V ±10%,
50 Hz ±0.1 Hz or 60 Hz ±0.1 Hz

Phase Sequence:

L1, L2, L3

Interval length:

10 minutes

Wye connection:

(l1, L2, L3 to N)

Power supply:

88 volts to 265 volts AC

 

Environmental Condition Ranges

Working Temperature

-10°C to 55°C; 14°F to 131°F

Operating Temperature

0°C to 35°C; 32°F to 95°F

Storage Temperature

-20°C to 60°C; -4°F to 140°F

Reference Temperature

23°C ±2K; 74°F ±2K

Relative Humidity

Class C2 acc. IEC 60654-1 (Model 1743)

Class C2 acc. IEC 60654-1 (Model 1744)

Class B2 acc. IEC 60654-1 (Model 1745)

Housing

Robust, fully insulated housing and accessories

Protection Type

IP65 as per EN 60529 (Model 1743)

IP65 as per EN 60529 (Model 1744)

IP50 as per EN 60529 (Model 1745)

Safety
 

IEC/EN 61010-1 600V CAT III, 300V CAT IV,
pollution degree 2, double insulated

Type Test Voltage

5.2 kV rms, 50 Hz/60Hz, 5 sec

EMC
 

Emission:

IEC/EN 61326-1, EN 55022

Immunity:

IEC/EN 61326-1

 
 

Voltage and Current Measurements

Input Voltage

 

Input range VIP-N:

maximum 480 V AC

Input range VIP-P:

maximum 830 V AC

Max. overload voltage:

1.2 VI

Input range selection:

by job programming

Connections:

P-P or P-N, 1- or 3-phase

Nominal voltage VN:

less than or equal to 999 kV with PTs and ratio

Input resistance:
 

approx. 820 KΩ per channel Lx-N single-phase (L1 or A, L2 or B, L3 or C connected) approx. 300 KΩ

Intrinsic uncertainty:

0.1% of VI

Voltage transformer:

ratio: <999 kV/V

Ration selection:

by job programming

Current Input with Flexi Set

 

Input ranges II L1 or A, L2 or B, L3 or CN:

15A /150A / 1500A / 3000A AC
 

Measuring Range:

0.75A to 3000A AC

Intrinsic uncertainty:

<2% of II

Position influence:
 

maximum ±2% of measured value - for distance conductor to measurement head >30mm

Stray field influence:
 

< ±2A AC for Iext=500A AC and distance to measuring head >200mm

Temperature coefficient:

<0.05%/k

Current transformer:

ratio less than or equal to 999 kA/II

Ratio selection:

by job programming

Connection:
 

3-phase, 3-phase +N, 2-phase L1 or A and L3 or C (2 Wire-meter-method) 7 pole connector

Current Input for Clamp

 

Input ranges II L1 or A,
 L2 or B, L3 or C, N:

0.5V nominal (for II) 1.4V peak
 

Intrinsic uncertainty:

<3% of II

Maximum overload:

10V AC

Input resistance:

Approx. 8.2KΩ

Current transformer:

ratioΩ 999kA/II

Power Systems

Delta, 2-Element Delta, Wye, Single-Phase, Split Single-Phase

 
 

Mechanical and General Specifications

 Power Supply   Functional range:

 

Power consumption:

Ride through model 1743:

Ride through model 1744:

Ride Through model 1745:

Fuse:
 

88V to 660V absolute, 50Hz/60Hz

100V to 350V DC internal fuse 630mA T

5 watts

3 second capacitor

3 second capacitor

Internal battery for typical > 5 hours ride through with intelligent power management

Power supply fuse can be replaced in service facility only.
Supply can be connected in parallel to measuring inputs (up to 660V)

Display Indicators

 

LED's for status and voltage levels
Fluke model 1745: LC-display with backlight for voltage, current, active power, phase sequence

Memory

Intervals:


 

Events:

Memory model:

Capacity 8 MB Flash-EPROM

A function >12000 intervals for >85 days with 10 minute intervals.
P function >30000 intervals for >212 days with 10 minute intervals.

>13000

linear, circular

Interface
 

RS232, 9600 ...115000 baud, automatic baud rate selection, 3-wire communication

Measurement

A/D converter:

Anti-aliasing filter:

Frequency response:

Interval length:

Averaging time for Min/Max values:

Time base

Resolution:

Deviation:

 

16 bit, sample rate: 10.24 kHz

FIR-Filter, fc=4.9 kHz

uncertainty <1 % of Vm for 40 Hz to 2500 Hz

1, 3, 5, 10, 30s, 1, 5,10, 15, 60 minutes

1/2, 1 mains period, 200 ms, 1, 3, 5 seconds
 

 

10ms (at 50Hz)

2s/day at 23°C (74°F) ±2K

Dimensions

Model 1743:
 

Model 1744:
 

Model 1745:
 

 

170mm (H) x 125mm (W) x 55mm (D)
69" (H) x 51" (W) x 22" (D)

170mm (H) x 125mm (W) x 55mm (D)
69" (H) x 51" (W) x 22" (D)

282mm (H) x 216mm (W) x 74mm (D)
115" (H) x 88" (W) x 33" (D)

Weight

Model 1743:

Model 1744:

Model 1745

 

2kg

2kg

3kg


Fluke | Hart | Reed | Yokogawa | EuroSMC | Kyoritsu | Megger | | Tenmars | Tektronix | Amprobe | CIE | Silvertronic |
 Site Map | Search | About Us | Contact Us

 

Rapid-Tech Equipment
ABN 79 883 184 102
1300 Ferntree Gully Road. Scoresby. Victoria 3179
P.O. Box 4243 Knox City Centre. Victoria 3152