1750 Series 3-Phase Power Quality Recorder - Specifications

 

Power Quality Measurement Standards

Conformance
 

IEC 61999-1-4 Class 1, IEC 61000-4-30 Class A or B depending on measurement function, IEEE519, IEEE1159, IEEE1459

Clock/calendar

Leap years, 24-hour clock

Real-time clock accuracy

not more than ±1 sec/day

Internal memory capacity for data

at least 1 GB

Maximum recording period

at least 31 days

Measurement time control

automatic

Maximum number of events

limited only by the size of the internal memory

Power requirements

100V to 240V rms ±10%, 47-63Hz, 40W

Operating time during interruptions (internal UPS operation)

5 minutes per interruption, 60 minutes total operating time without recharging

Dimensions

215mm x 310mm x 35mm  (8.5" x 12.2" x 3.5")

weight

6.3kg (14lb)

 
 

Input

Measurement types

 

One Phase plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta, 21/2 Element Wye.

Voltage Input channels

4 AC/DC 

Current Input channels

5 channels

Voltage channels
 

Input resistance: 2MΩ
Input capacitance: <20pF

Current input characteristics
 

2V rms= full scale, 1MΩ input impedance for ferro CT's, low impedance for Flexi-CT's

Measuring method

 

Simultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal frequency references used during voltage drops.

 
 

Synchronization and Sampling

PLL synchronization source

 

The PLL synchronizes to the A-N voltage for Wye power types, and to the A-B voltage for Delta power types. All listed power types can be characterized as either Wye or Delta.

PLL lock range

42.5 to 69Hz

Sampling frequency

 

Voltage and current: 2.56 samples/cycle inter-harmonics per IEC61000-4-7: 2 560points/10 cycles (50Hz), 3072 points/12 cycles (60Hz) Transient Voltage: 5MHz

A/D resolution:
 

Voltage and current: 24 bits
Transient voltage: 14 bits

 
 

Voltage and Current Measurements

AC voltage range

1000V rms ±10% over range

DC voltage range

±1000V rms +10% over range

Voltage crest factor

3 or less

Current measurement range

Depends on current probe used

Current crest factor

4 or less

 
 

RMS Voltage Measurement

Measurement type

 

True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60Hz respectively, as required by IEC 61000-4-30.

Measurement uncertainty
 

AC: ±0.2% of reading ±0.1% of full scale, above 50V rms.
DC: ±0.5% of reading ±0.2% of full scale, above 50V dc.

 
 

RMS Current Measurement

Measurement type

 

True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60Hz respectively, as required by standards.

 
 

Transient Voltage (Impulse)

Measurement type

Waveshape sampling

Full scale

8000 Volts peak

Sample resolution

200nS

Measurement uncertainty
 

±5% of reading ±20 V (test parameters: 1000 V DC,
1000V rms, 100 kHz)

 
 

Voltage Swells (RMS swell)

Measurement type

 

True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines).

Displayed data

Amplitude and duration of swell

Measurement

Same as rms voltage

 
 

Voltage Dip (RMS sag)

Measurement type

 

True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines).

Displayed data

Amplitude and duration of dip or interruption

Measurement

Same as rms voltage

 
 

Voltage Dropout (interruption)

Measurement type

Same as voltage dip

 
 

LAN Interface

Connector

RJ-45

Speed and type

10/100 Base-T, auto MDIX

Communications protocol

TCP/IP over Ethernet

 
 

Wireless Controller Interface

Connection

wireless (2.4 GHz radio)

Speed

up to 700 kbit/second

Communication protocol

Bluetooth SPP

 
 

Power Measurement

Measurement type
 

True rms calculated continuously: every cycle, and every 10 or 12 cycles at 50 or 60Hz respectively, as required by standards.

 
 

Frequency Measurement

Measurement range

42.5 to 69 Hz

Measurement source

Same as PLL synchronization source

Measurement accuracy

±10MHz (10 to 110% of range, with sine wave).

 
 

Power Factor

Measurement range

0.000 to 1.000

Measure accuracy

±1 digit from the calculation of each measured value (±3 digits for total)

 
 

Displacement Power Factor

Measurement method
 

Calculated from the phase difference between voltage fundamental and current fundamental

Measurement range

-1000 (leading) to +1000 (lagging)

Measurement accuracy

±0.5% of reading ±2% of full scale ±1 digit

 
 

Voltage Unbalance and Phase Sequence

Measurement method
 

Positive sequence voltage divided by negative sequence voltage, per IEC 61000-4-30

 
 

Harmonic Voltage and Current

Analysis window

Rectangular

Analysis order

1st to 50th order

Measurement accuracy

Voltage/Current 1st to 0th orders: ±0.5% of reading ±0.2% of full scale, 2nd 1st to 50th orders: ±1% of reading ±0.3% of full scale (current sensor accuracy must be included for current and power)

Measurement method

IEC 61000-4-7

 
 

Inter-harmonic Voltage and Current (intermediate harmonics)

Analysis window

Rectangular

Analysis orders

1.5 to 49.5th order

Measurement method

IEC 61000-4-7

 
 

Environmental Specifications

Operating environment

Indoors or in covered area outdoors, up to 2000m altitude

Storage temperature

-20°C to 50°C

Operating temperature

0°C to 40°C

Humidity

80% RH maximum non-condensing

 
 

Electrical Safety

EMC

 

EN 61326-1: 1997+A1: 1998 Class A
EN 61000-3-2: 1995+A2: 1998
EN 61000-3-3: 1995

Safety

 

EN 61010-1-2nd Edition: 2000
Voltage input unit: Contamination Level 2, Overvoltage Category 1000V CAT III, 600V CAT IV (anticipated overvoltage: 8000V)

 
 

Maximum Rated Working Voltage

Voltage terminals

1100 volts rms

Voltage durability

5550 Vrms AC for 1 minute, between voltage input terminals, voltage input terminals and current probes, and voltage input terminals and case (50/60Hz, 1mA sense current).

Enclosure protection

IP30 (per EN60529

 