| Technical Specifications |
|
Overview of Measurement Functions |
|
Extended
Evaluation |
Power quality
statistics according to EN 50160 and DISDIP
tables like ITIC CEBEMA, ANSI |
|
Event List
|
Dips, swells and
interruptions are detected and stored in the
event list. Also any trigger which fires
generates an event added to this list.
The Event list shows the exact time when the
event occurred as well as the duration and
magnitude. Sorting by several attributes of
these events is possible to select one for
further root cause analysis.
RMS values, transients and fast transients can
be stored if a trigger fires. |
|
Continuous
Recording
|
Fluke 1760 records
rms values together with corresponding minimum
and maximum values for:
|
|
Triggered
Recording
|
|
RMS: |
Aggregation
time is adjustable between 10ms (1/2
cycle), |
| |
20ms (1
cycle), 200ms (10/12 cycles) or 3
seconds (150/180 cycles) |
| |
Calculating
RMS values, Harmonics and
Inter-harmonics is performed |
| |
synchronous
to the power frequency. Basic
aggregation for harmonics |
| |
and
inter-harmonics is 200ms. |
|
Oscilloscope: |
Sample rate
is 10.24 kHz for all eight channels. |
|
Fast
Transients: |
Sample rate
is selectable from 100kHz to 10MHz for
channels 1 to 4 |
| |
FFT of Fast
Transients |
|
|
Mains
Signalling |
Phases and
N-conductor, Voltage and Current |
|
Online Mode
|
Variable refresh
rate. This feature allows verification of
instrument set up and delivers a quick
overview of oscilloscope, transients and
events. |
|
| |
| |
|
General Data |
|
Intrinsic
Uncertainty |
Refers to
reference conditions and is guaranteed for two
years |
|
Quality System |
Developed,
manufactured as per ISO 9001: 2000 |
|
Environmental
Conditions
|
|
Operating
Temp Range: |
0°C
to +50°C (32°F
to +122°F) |
|
Working
Temp Range: |
-20°C
to +50°C (-4°F
to +122°F) |
|
Storage
Temp Range: |
20°C
to +60°C (-4°F
to 140°F) |
|
Reference
Temperature: |
23°C
±2K (74°F
±2K) |
|
Climatic
Class: |
B2 (IEC
654-1), -20°C
to +50°C (-4°F
to +122°F) |
|
Max.
Operating Altitude: |
2000m: max.
600V CAT IV*, power supply: 300V CAT III |
| |
5000m: max.
600V CAT III*, power supply: 300V CAT II |
| |
* depending
on sensor |
|
|
Reference
Conditions |
|
Environmental Temp: |
23°C
±2K (74°F
±2K) |
|
Power
Supply: |
230V
±10% |
|
Power
Frequency: |
50Hz/60Hz |
|
Signal: |
Declared
input voltage Udin |
|
Averaging: |
10 minute
intervals |
|
|
Housing |
Insulated, robust
plastics housing |
|
EMC |
|
Emission: |
Class-A as
per IEC/EN 61326-1 |
|
Immunity: |
IEC/EN
61326-1 |
|
|
Power Supply
|
|
Range: |
AC: 83V to
264V (45Hz to 65Hz) |
| |
DC: 100V to
375V |
|
Safety: |
IEC/EN
61326-1 2nd edition |
| |
300V CAT III |
|
Power
Consumption: |
Maximum 54VA |
|
Battery
Pack: |
NiMH, 7.2V,
2.7 AH |
| |
In case of a
power supply failure an internal battery
|
| |
maintains
the supply for up to 40 minutes.
Afterwards, or |
| |
in case of
discharged accumulators the Fluke 1760
is turned |
| |
off and
continues the measurement with the
latest settings |
| |
as soon as
the supply voltage returns. the battery
can be |
| |
replaced by
the user. |
|
|
Display
|
| |
Fluke 1760
features LED indicators for the status
of the |
| |
eight
channels, phase sequence, power supply
(mains or |
| |
accumulation), memory usage, time
synchronization, and |
| |
data
transfer. |
|
Power
LED: |
● Permanent light:
normal power supply from mains. |
| |
● OFF: Supply via
internal accumulator in case of a power |
| |
failure. |
|
Channel
LED's: |
3-color
LED's per channel for: |
| |
● Overload
condition |
| |
● Under load
condition |
| |
● Signal level in
normal range |
|
|
Data Memory |
2 GB Flash memory
depending on model |
|
Memory Model |
Linear |
|
Interfaces
|
Ethernet
(100MB/s), compatible to Windows®
98/ME/NT/2000/EP RS-232 external modem via
RS-232. |
|
Baud Rate for
RS-232 |
9600 Baud to 115
kBaud
|
|
Dimensions |
325mm (H) x 300mm
(W) x 65mm (D) |
|
Weight |
4.9 kg (without
accessories) |
|
Calibration
Interval |
One year
recommended for Class-A, otherwise 2-years |
|
Warranty |
Two years |
|
| |
| |
|
Signal Conditioning |
|
Range for 50Hz
Systems |
50Hz
±15% (42Hz to
57Hz) |
|
Range for 60Hz
Systems |
60Hz
±15% (51Hz to
69Hz) |
|
Resolution |
16 ppm |
|
Sampling
Frequency for 50Hz Power Frequency |
10.24 kHz, the
sampling rate is synchronized to mains
frequency
|
|
Uncertainty for
Frequency Measurements |
less than 20 ppm
|
|
Uncertainty of
Internal Clock |
less than 1
second/day
|
|
Measurement
Intervals
|
|
|
Aggregation
of the internal values as per IEC
61000-4-30 |
|
|
Class -A |
|
Min/Max
Values: |
Half-cycle,
e.g.: 10ms values at 50Hz |
|
Transients: |
sample rate
100kHz to 10MHz per channel |
|
|
Harmonics |
as per IEC
61000-4-7: 2002: 200ms |
|
Flicker |
as per IEC
61000-4-15: 2003: 10 minutes (Pst), 2 hours
(Pit) |
|
| |
| |
|
Measurement Inputs |
|
Number of
Inputs |
8 galvanically
isolated inputs for voltage and current
measurements. |
|
Sensor Safety |
Up to 600V CAT IV
depending on sensor |
|
Basic Safety |
300V CAT III |
|
Nominal Voltage
(RMS) |
100mV |
|
Range (peak
value) |
280mV |
|
Overload
Capacity (RMS) |
1000V,
continuously |
|
Voltage Rise
Rate |
Maximum 15kV/µs |
|
Input
Resistance |
1 MΩ |
|
Input
Capacitance |
5 pF |
|
Input Filter
|
Each channel is equipped with a passive
low-pass filter, an anti-aliasing filter and a
16-bit A/D converter. All channels are sampled
synchronously with a common quartz-controlled
clock pulse.
The filters protect against voltage transients
and limit the signal rise, reduce high
frequency components and especially the noise
voltage above half the sampling rate of the
A/D converter by 80dB, thus achieving very
small measuring errors in an exceptionally
large amplitude range. This is also valid
under extreme operating conditions like
transient voltages at the output of
converters. |
|
| |
| |
|
Uncertainties |
|
Uncertainty at
reference Conditions
|
|
|
Uncertainty
including the voltage sensors is in
compliance |
|
|
with IEC
61000-4-30 Class-A. All voltage sensors
are |
|
|
suitable for
DC up to 5kHz |
|
With
Sensor 1000V |
0.1% at Udin
+ 480V and 600V P-N |
|
With
Sensor 600V |
0.1% at Udin
= 230V P-N |
|
|
Intrinsic
Uncertainty for Harmonics |
Class 1 as per EN
61000-4-7:2002
|
|
Reference
Conditions
|
23°C
±2K <60% R.H. (74°F
±2K <60% R.H.)
Warmed up instrument >3 hours
Power Supply: 100V to 250V ac |
|
Temperature
Drift |
100 ppm/K |
|
Aging |
<0.05%/year |
|
Common Mode
Rejection |
100dB at 50Hz |
|
Temperature
Drift |
Change of
amplification through temperature: <0.005%/K |
|
Aging |
Change of
amplification through ageing: <0.04%/year |
|
Noise |
Noise voltage,
Input short-circuited: <40µV |
|
DC |
±(0.2% of reading
+ 0.1% sensor) |
|
|
|
|
|