Model i30 Features |
|
i30
AC/DC Current Clamp for use with Multimeters, Recorders and
other suitable recording instruments.
|
|

|
Features
|
|
|
|
|
Technical Specifications |
|
Current Range |
20 Amps AC rms or DC |
|
Measuring Range |
±30 Amps |
|
Output Sensitivity |
100mV/A |
|
Accuracy (at 25°C) |
±1% of reading ±2mA |
|
Resolution |
±1 mA |
|
Load Impedance |
> 10KΩ and
≤100pF |
|
Conductor Position
Sensitivity |
±1% relative to center reading |
|
Frequency Range |
DC to 20kHz (-0.5db) |
|
Temperature Coefficient |
±0.01% of reading/°C |
|
Power Supply |
9 volt Alkaline, MN1604/PP3, 30
hours, low battery indicator. |
|
Working Voltage |
300 Volts AC rms or DC (see
Safety Standards section) |
|
| |
|
Safety Standards |
|
Safety Standards |
BS EN 61010-1: 2001
BS EN 61010-2-203: 2002
BS EN 61010-031: 2002
300 Vrms, Category III, Pollution Degree 2
Use of the probe on uninsulated conductors is limited to 300
volts ACrms or DC and frequencies below 1kHz. |
|
EMC Standards |
EN 61326: 1998 +A1, A2, and A3 |
|
| |
| |
|
General Specifications |
|
Maximum Conductor Size |
19mm diameter |
|
Output Connection |
4mm safety connector |
|
Output Zero |
Manual adjust via thumbwheel |
|
Cable length |
1.5 meters |
|
Operating Temperature Range |
0°C to
+50°C |
|
Storage Temperature Range |
-20°C to
+85°C (with battery removed) |
|
Operating Humidity |
15% to 85% (non-condensing) |
|
Weight |
250g |
|