Rapid-Tech Equipment Logo Combo Kit Power Quality Recorder Power Quality Analyzer Multifunction Digital Multimeter

Nationwide - Call 1800 358 531 

Kyoritsu Instruments Logo Model 4106 Earth Resistance/Resistivity Tester
 
Earth  Testers

Model 4106 Earth Resistance/Resistivity Tester

 

 

 

 

Features

  • High test current up to 80mA yielding resolution of 0.001Ω on 2Ω range.
  • Advanced filtering method, based on Fast Fourier Transform (FFT) reduces noise interference for obtaining stable measurements.
  • Automatic and Manual selection of the Test Current Frequency in four bands (94/105/111/128Hz) in Automatic mode, the 4106 will select the most suitable frequency.
  • Several sub-results can be shown on the display. Resistance of the Auxiliary Earth Spikes, Frequency of the Test Current Voltage and Frequency of Interference (noise), Residual Resistance Rk, etc.
  • Warning for excessive noise and high Auxiliary Earth Spikes resistance.
  • Large Graphic Display with backlight for reading in poorly illuminated areas.
  • Up to 800 measurement results can be saved in the memory and recalled on the display.
  • The stored results can be transmitted to a PC using the 'KEW Report' software and a USB adaptor both of which are included.
  • Robust design with IP54 protection.

    CE Certified

 

Specifications
Function Range Resolution

Measuring Range

Accuracy
Earth Resistance (RE)
(Rg at p measurement)
0.001Ω 0.03Ω to 2.099Ω ±2% of rdg ±0.03Ω
20Ω 0.01Ω 0.03Ω to 20.99Ω ±2% of rdg ±5 dgt
(note1)
200Ω 0.1Ω 0.3Ω to 209.9Ω
2000Ω 1Ω 3Ω to 2099Ω
20kΩ 10Ω 0.03Ω to 20.99
200kΩ 100Ω 3Ω to 209.9Ω
Auxiliary Earth Resistance (Rh, Rs)       8% of Re+Rh+Rs
Earth Resistivity ρ 0.1Ω•m to 1Ω•m
Autoranging
0.02 to 395.6Ω•m ρ=2×π×a×Rg
(note2)
20Ω 0.02 to 3956Ω•m
200Ω 20 to 39.56•m
2000Ω 0.2 to 395.6•m
20kΩ 2.0 to 1999kΩ•m
200kΩ 2.0 to 1999kΩ•m
Series Interference Voltage
Ust (AC only) (note3)
50V 0.1V 0 to 50.9 Vrms ±2% of rdg ±2 dgt
(50/60Hz)
±3% of rdg ±2 dgt
(40 to 500Hz)
Frequency
Fst
Autoranging
 
0.1Hz
1Hz
40Hz to 500Hz ±1% of rdg ±2 dgt
 
Note1: Auxiliary earth resistance is 100Ω with Rk correction.
Note2: Depending on the measured Rg. Interval [a] between auxiliary earth spikes is 1.0 to 30.0m.
Note3: This instrument is NOT designed to measure line voltages on commercial powers.
 
 
Measuring Method
Earth Resistance Fall-of-potential method (currents and voltages measured via Probes)
Earth Resistivity (ρ) Wenner 4-pole method
Series Interference Voltage
(Earth Voltage)
RMS Rectifier (between the E-S Terminals)
 
 
Other Specifications
Memory Capacity 800 data
Communication Interface USB optical adaptor (Model 8212-USB)
LCD Readout Dot-matrix 192 x 64 monochrome
Over-range Indication "OL"
Overload Protection between E-S (P) and between E-H (C) terminals (280 volts AC for 10 sec.)
Withstand Voltage between electrical circuits and enclosure (3540 volts AC 50/60Hz for 5 sec.)
Applicable Standards IEC 61010-1 CAT. III 300V, CAT. IV 150V, Pollution Degree 2
IEC 61010-031, IEC 61557-1,5, IEC 61326-1 (EMC), IEC60529 (IP54)
 
 
General Specifications
Power Source (DC 12V) Eight type 'AA' manganese dry batteries (R6P). Auto power off approx 5 min.
Dimensions 167mm (L) x 185mm (W) x 89mm (D)
Weight approx. 900g (including batteries)
 
 
Ordering Information
Model 4106




 
Earth Resistance/Resistivity Tester supplied with: Precision Measurement test leads (#7229), Simplified Measurement test leads (#7238), Auxiliary Earth Spikes [2 spikes/set]x2 sets (4 spikes in total) (#8032),
Cord Reel [4 pcs]x1 set, USB adaptor with "KEW Report Software" (#8212-USB), Shoulder strap (#9121), Carrying Case (#9125), R6P x 8 batteries, Instruction manual, and Calibration Certificate.
 
 
Optional Accessory
Model 8212-RS232C RS-232C adaptor with "KEW Report Software"

 


Fluke | Hart | Reed | Yokogawa | EuroSMC | Kyoritsu | Megger | | Tenmars | Tektronix | Amprobe | CIE | Silvertronic |