Features

  • The earth resistance from 0.05Ω to 1200Ω can be measured without the auxiliary earth spikes. (The Multiple Earthing System).
  • True RMS: Accurate true RMS readings of AC current including distorted waveform from 1mA to 30.0A.
  • Noise Check Function: A function to detect current, which effects on an earth resistance measurement and display 'NOISE' mark on the LCD.
  • Memory Function: Save and display up to 100 measurement data.
  • Data Hold function, Buzzer function, Back Light function.
  • Compliant with Safety Standards of IEC 61010-1: CAT. IV 300V Pollution Degree 2.

    (Note: A single earthing can not be measured. (Only for Multiple Earthing System).

    CE Certified True RMS

 

Specifications
Function Range Resolution

Measuring Range

Accuracy
Earth Resistance  (Auto Range) 0.01Ω (note1) 0.00Ω to 20.99Ω ±1.5% rdg ±0.05Ω
200Ω 0.1Ω 16.0Ω to 99.9Ω ±2% of rdg ±0.5Ω
100.0Ω to 209.9Ω ±5% of rdg ±2Ω
1200Ω 1Ω 160Ω to 399Ω ±5% of rdg ±5Ω
400Ω to 599Ω ±10% of rdg ±10Ω
10Ω 600Ω to 1260Ω ----
AC Current
(50Hz/60Hz) Auto Range
100mA 0.1mA 0.0 to 104.9mA ±2% of rdg ±0.7mA
1000mA 1mA 80 to 1049mA ±2%
10A 0.01A 0.80 to 10.49A
30A 0.1A 8.0 to 31.5A
 
Note1: 4 counts or less are corrected to 0.
Note: Crest Factor ≤3 (50Hz/60Hz, peak value shall not exceed 60A).
 
Operating System
Earth Resistance Function Constant Voltage Injection
Current Detection
(Frequency: Approx. 2400Hz)
Dual Integration
AC Current Function Successive Approximation
 
 
Other Specifications
Over-range Indication "OL" is displayed when input exceeds the upper limit of a measuring range.
Response Time Approx. 7 seconds (Earth Resistance)
Approx. 2 seconds (AC Current)
Sample Rate Approx. 1 times per second
Auto Power-off Turns power off about 10 minutes after last button operation
Withstand Voltage Between transformer jaws fitted parts and Case enclosure, (except for jaws) (5320 volts AC 50/60Hz for 5 sec.)
Applicable Standards IEC 61010-1: 2001 ( CAT. IV 300V, Pollution Degree 2
 
General Specifications
Conductor Size Approx. 32mm maximum
Power Source (DC 6 volts) R6P size 'AA' manganese batteries x 6 pcs.
Current Consumption Approx. 50mA (max. 100mA).
Dimensions 246mm (L) x 120mm (W) x 54mm (D)
Weight 780g (including batteries)
 
 
Ordering Information
Model 4200 Earth Clamp Tester. Includes: Resistor for Operation Check Qty 1. (#8304), One Hard Case (#9128), and Instruction manual.

 