Model 4200 Earth
Clamp Tester |
|
|
|
|
Earth Testers |
|
 |
Features
- The earth resistance from 0.05Ω
to 1200Ω can be measured without the
auxiliary earth spikes. (The Multiple Earthing System).
- True RMS: Accurate true RMS readings of
AC current including distorted waveform from 1mA to 30.0A.
- Noise Check Function: A function to
detect current, which effects on an earth resistance measurement
and display 'NOISE' mark on the LCD.
- Memory Function: Save and display up to
100 measurement data.
- Data Hold function, Buzzer function,
Back Light function.
- Compliant with Safety Standards of IEC
61010-1: CAT. IV 300V Pollution Degree 2.
(Note: A single earthing can not be measured. (Only for
Multiple Earthing System).

|
|
|
Specifications |
|
Function |
Range |
Resolution |
Measuring Range |
Accuracy |
|
Earth Resistance (Auto Range) |
2Ω |
0.01Ω (note1) |
0.00Ω to 20.99Ω |
±1.5% rdg ±0.05Ω |
|
200Ω |
0.1Ω |
16.0Ω to 99.9Ω |
±2% of rdg ±0.5Ω |
|
100.0Ω to 209.9Ω |
±5% of rdg ±2Ω |
|
1200Ω |
1Ω |
160Ω to 399Ω |
±5% of rdg ±5Ω |
|
400Ω to 599Ω |
±10% of rdg ±10Ω |
|
10Ω |
600Ω to 1260Ω |
---- |
AC Current
(50Hz/60Hz) Auto Range |
100mA |
0.1mA |
0.0 to 104.9mA |
±2% of rdg ±0.7mA |
|
1000mA |
1mA |
80 to 1049mA |
±2% |
|
10A |
0.01A |
0.80 to 10.49A |
|
30A |
0.1A |
8.0 to 31.5A |
|
|
|
| Note1: |
4 counts or less are corrected to 0. |
| Note: |
Crest Factor ≤3 (50Hz/60Hz, peak value
shall not exceed 60A). |
|
|
|
|
Operating System |
|
Earth Resistance Function |
Constant Voltage Injection |
|
Current Detection |
|
(Frequency: Approx. 2400Hz) |
|
Dual Integration |
|
AC Current Function |
Successive Approximation |
|
|
|
|
|
|
Other Specifications |
|
Over-range Indication |
"OL" is displayed when input exceeds the upper limit of a measuring
range. |
|
Response Time |
Approx. 7 seconds (Earth Resistance)
Approx. 2 seconds (AC Current) |
|
Sample Rate |
Approx. 1 times per second |
|
Auto Power-off |
Turns power off about 10 minutes after last button operation |
|
Withstand Voltage |
Between transformer jaws fitted parts and Case enclosure, (except
for jaws) (5320 volts AC 50/60Hz for 5 sec.) |
|
Applicable Standards |
IEC 61010-1: 2001 ( CAT. IV 300V, Pollution Degree 2 |
|
|
|
|
General Specifications |
|
Conductor Size |
Approx. 32mm maximum |
|
Power Source (DC 6 volts) |
R6P size 'AA' manganese batteries x 6 pcs. |
|
Current Consumption |
Approx. 50mA (max. 100mA). |
|
Dimensions |
246mm (L) x 120mm (W) x 54mm (D) |
|
Weight |
780g (including batteries) |
|
|
|
|
|
|
Ordering Information |
|
Model 4200 |
Earth Clamp Tester. Includes: Resistor for Operation Check
Qty 1. (#8304), One Hard Case (#9128), and Instruction manual. |
|