MIT480 Series Telecommunications Insulation Tester - Specifications

 

Insulation Ranges (20°C)
Nominal Test Voltage
 
50V 100V       for Model MIT480
50V, 100V, 250V 500V, 1000V for Models MIT481, MIT485
Insulation Resistance Range
 
10GΩ for Model MIT480
200GΩ for Models MIT481, MIT485
Full Scale Accuracy





 
±2% ±2 digits up to 100MΩ on all ranges on all Ranges
Then:
50 volts ±3% ±2 digits ±4.0% GΩ
100 volts ±3% ±2 digits ±2.0% GΩ
250 volts ±3% ±2 digits ±0.8% GΩ
500 volts ±3% ±2 digits ±0.4% GΩ
1000 volts ±3% ±2 digits ±0.2% GΩ
Test Current on Load
 
1mA at minimum pass values of insulation as specified in
BS 7671, HD 384, IEC 364, 2mA maximum
Short Circuit Current 2mA +0% -50%
Terminal Voltage -0% +20% ±1V
Leakage Current Ranges 10µA, 2000µA
Leakage Current Accuracy 10% ±3 digits
Analog Range 1GΩ full scale
Voltage Display Accuracy 3% ±3 digits ±0.5% of rated voltage
Polarization Index (PI) 10 min/1 minute ratio
Dielectric Absorption Ratio (DAR) 60 sec/30 sec ratio
   
Note: All ranges measure from 0,00MΩ upwards.
  Above specifications only apply when high quality silicone leads are being used.
 
Continuity Ranges
Measuring Range 0.01Ω to 99.9Ω (0Ω to 100Ω on analog scale)
Accuracy (at 20°C) ±2% ±2 digits (0Ω to 100Ω)
Open Circuit Voltage 5V ±1V
Test Current
 
205mA (-0mA +20mA) (0.01Ω to 9.99Ω)
20mA (±1mA) (10.0Ω to 99.9Ω)
Zero Offset at Probe Tips 0.10Ω typical
Lead Resistance Zeroing Up to 9.99Ω
Buzzer Variable limit 1Ω, 2Ω, 5Ω, 10Ω, 20Ω
 
 
Resistance
Measuring Range 0.01kΩ to 1000kΩ (0Ω to 1MΩ on analog scale)
Accuracy (at 20°C) ±3% ±2 digits up to50kΩ then ±2 digits
Open Circuit Voltage 5V ±1V
Short Circuit Current 1.5mA ±0.2mA
 
 
Capacitance Measurement (Models MIT481, MIT485)
Measuring Range 100pF to 10µF
Accuracy ±5% ±2 digits
Distance by Capacitance
 
Arithmetic conversion from capacitance measurement on
Default capacitance measurement: 50nF/km
Capacitance Range 40nF/km to 60nF/km
 
 
Voltage Range
DC Volts 0 to 600V (±2% ±2 digits)
AC True RMS 10mV to 600V sinusoidal (40Hz to 400Hz) (±2% ±2 digits)
Analog Scale
Unspecified Input Level
0 to 1000V
0 to 10mV (40Hz to 400Hz)
For Non-Sinusoidal Waveforms additional Specifications Apply:
101mV to 600V True RMS ±3% ±2 digits
10mV to 100mV ±8% ±2 digits
Default Voltmeter Operates at > 25V AC or DC on any range except OFF
Frequency 40Hz to 450Hz

Accuracy

±0.5% ±1 digit
 
 
Storage Result
Capacity > 1000 test results for Model MIT481, MIT485
Download Bluetooth wireless for  Model MIT485
Bluetooth Class Class II
Range up to 10 meters
 
 
Environmental
Operating Temperature -25°C to +55°C
Humidity
 
95% RH at -0°C to +35°C
70% RH at +35°C to +55°C
Storage Temperature -30°C to +80°C
Calibration Temperature +20°C
Maximum Altitude 2000 meters
Dust and Water Protection IP54
 
 
Safety
Safety Protection Meets IEC 61010-1 to 600V phase to earth. Category IV. Reference to safety warning supplied
EMC In accordance with IEC 61326-1
Fuse Protection Use only a 500mA (FF) 1000V 32mm x 6mm ceramic high breaking capacity
HBC 50kA minimum. (GLASS FUSES MUST NOT BE USED)
 
 
General Specifications
Power Supply
 
5 x 1.5V cells type IEC LR6 (AA, MN1500, HP7, AM3, R6HP) Alkaline
NiMH rechargeable cells may be used
Battery Life
 
2200 insulation tests with duty cycle of 5 seconds ON, 55 seconds OFF
@ 1000V into 1MΩ
Instrument Dimensions 220mm (L) x 92mm (W) x 50mm (D)
Instrument + Case 456mm (L) x 178mm (W) x 89mm (D)
Weight (Instrument only) 590gms
Weight (Instrument + Case) 1.75kg

 