Model DET4TD2
and DET4TDR2 Earth/Ground Testers |
|
|
With the ability to conduct soil resistivity, and 2 and 3 pole earth
electrode testing the DET4TD2 offers the user full flexibility with an
increased measurement range.
|
|
 |
Four-pole soil
resistivity testing
Features
- IP54 rated.
- Now with extended 20kΩ measurement
range.
- 2, 3 and 4 point testing.
- Selectable 25V or 50V output.
- Dry cell or rechargeable versions. (For rechargeable battery
order Model DET4TDR2)
- Complete with stake and wire kit.
- Right angle terminal adaptors (to connect bare wires to
terminals).
- Simple one button operation.
- Hard wearing carry case.
- Delivered with calibration certificate.
|
|
Specifications |
|
Display |
3.5" high contrast LCD |
|
Ingress Protection |
IP54 |
|
C Spike, P Stake and noise Check |
Automatic |
|
Noise Rejection |
40V peak to peak |
|
2-Wire, 3-Wire Test, 4-Wire Test |
Yes, no shorting links required |
Instrument Output
|
Voltage: |
|
Current: |
|
±25V or ±50V at 128 Hz |
|
4.5mA or 0.45mA |
|
Earth Voltage |
0V to 100V |
|
Resistance |
Range: 0.01Ω to 20KΩ |
Accuracy: |
2P measurements |
2% ±3 digits |
|
3P measurements |
2% ±3 digits |
|
4P measurements |
2% ±3 digits |
Maximum Probe Resistance
(50V output voltage) |
Rp Limit: 100kΩ |
Limits reduced to 50kΩ for 25V output voltage
Limits reduced to 50kΩ for 0.01Ω
resolution |
|
Rc Limit: 100kΩ |
|
Ground Voltage |
Range: 0V to 100V AC |
Accuracy: |
2% ±2 volts |
|
|
|
|
|
|
Environmental Specifications |
|
EMC |
In accordance with IEC 61326-1 |
|
Operating Temperature |
-15°C to +55°C |
|
Storage Temperature |
-40°C to 70°C |
|
|
|
|
|
|
Safety |
|
Complies with the requirements |
of
EN 61010-1 CAT IV 100V between terminal pairs |
|
|
|
|
|
|
Standards |
|
Standards Compliance |
Complies with the requirements of KEMA K85B.
Complies with the following parts of EN 61557,
"Electrical safety in low voltage distribution systems up to 1000V
AC and
1500V DC - Equipment for testing, measuring or monitoring of
protective measures".Part 1. General requirements
Part 2. Resistance to earth |
|
|
|
|
|
|
General Specifications |
Power
|
8 X type 'AA' LR6 batteries (Model DET4TD2), and 8 x type 'AA' (LR6)
NiMH rechargeable batteries for (Model DET4TDR2) |
Dimensions
|
203mm (W) x 148mm (H) x 78mm (D)
8" (W) x 5.7" (H) x 3.2" (D) |
|
Weight |
1kg |
|
|
|
|
|
|
Ordering Information |
Ordering Code 1000-347
|
Megger Model DET4TD2 Tester 2, 3 and 4 terminal, complete with stake and wire kit
(15m, 10m, 3m), Right angle terminal adaptors, 8
type 'AA' batteries, carrying case and operating instructions. |
|
Ordering Code 1000-324
|
Megger Model DET4TDR2 Tester 2, 3 and 4 terminal, complete with stake and wire kit
(15m, 10m, 3m), Right angle terminal adaptors, 8
type 'AA' LR6 NiMH rechargeable batteries, external AC/DC
charger unit, carrying case and operating instructions. |
|
|
|
|
|
|
Optional Accessories |
|
Catalog # 5410-429 |
Replacement hard carry case |
|
Catalog # 6220-803 |
Right angled terminal adaptor set |
|
Catalog # 6220-804 |
2 replacement earth test spikes (200mm, 80mm dia.) |
|
Catalog # 6220-806 |
4 replacement test leads (15m, 10m, 10m, 3m) |
|
Catalog # 6220-824 |
Calibration check box (25 ohm) |
|
Catalog # 6220-850 |
1 x Black crocodile clip |
|
Catalog # 6320-245 |
Professional ground testing kit (2 x 50m, 2 x 30m, 4 x auger stakes,
tape measure, in hard carry case. |
|
Catalog # 6280-375 |
Vehicle 12 volt socket charger (rechargeable models only) |
|
Catalog # 21500-072 |
'Getting down to earth' A Megger guide to earth testing. |
|
|
|