Rapid-Tech Equipment Logo Combo Kit Power Quality Recorder Power Quality Analyzer Multifunction Digital Multimeter

Nationwide - Call 1800 358 531 

Megger logo

MIT300 Series Insulation Tester - General Specifications

Insulation Ranges
Nominal Test Voltage
 
1000V, 500V, 250V (D.C.) for Models MIT310, MIT320, MIT330
500V, 250V (DC) for Model MIT300
Measuring Ranges 10kΩ to 999MΩ on all Instruments
Short Circuit Current 1.5mA nominal
Test Current on Load >1mA at minimum pass values of insulation as specified in
BS 7671, HD 384, IEC 364
Accuracy


 

 

±3% of reading ±2 digits up to 10MΩ

for Models
MIT300, MIT310, MIT320, MIT330

±5% of reading ±2 digits up to 100MΩ
±30% up to full scale
   
±2.5% of scale or 

for Model MIT310A

30% of reading 200k to 10MΩ
Terminal Characteristics
Megger MIT300 Insulation and Continuity Tester Terminal Characteristics
 
 
Continuity Ranges
Measuring Range 0.01Ω to 99.9Ω (0Ω to 50Ω on analog scale)
Open Circuit Voltage 5V ±1V
Short Circuit Current 205mA ± 10mA -5mA for Models MIT300, MIT310, MIT320, MIT330
200mA to 250mA for Model MIT310A
Accuracy (at 20°C)
 
±3% ±2 digits for Models MIT300, MIT310, MIT320, MIT330
±2.5% of scale length or 30% of reading 0.2Ω to 2kΩ
for Model MIT310A
 
 
Specifications
Zero Offset Adjust
 
0Ω to 9Ω for Models MIT300, MIT310, MIT320, MIT330
0Ω to 0.5Ω for Model MIT310A
Continuity Buzzer



 
Operates at < 5Ω for Models MIT300, MIT310
Adjustable 1Ω to 20Ω for Models MIT320, MIT330
Operates at < 5Ω for Model   MIT310A
Response time <20ms for Models MIT300, MIT310, MIT320, MIT330
Response time <100ms for Model   MIT310A
Default Voltmeter
(all models except OFF)


 
> 25V AC or DC is applied display will operate as a voltmeter
for Models MIT310, MIT320, MIT330
Beeps and flash 'V' on display for Model MIT300
All models including OFF for Model MIT310A
Test Inhibit If more than 50 volts is detected, testing will be inhibited
Voltmeter Range 0 to 600V at 50/60Hz and DC
Voltmeter Accuracy
at 20°C (DC or AC)
±1% ± 2 digit) for Models MIT300, MIT310, MIT320, MIT330
±2.5% of scale length for Model MIT310A
Auto Power Down Operates after 10 minutes if left in standby mode MIT310, MIT320, MIT330
Automatic Discharge

 
After an insulation test the item under test will be discharged automatically. Any voltage present will be indicated on the display so that the discharge can be monitored.
Download Tests to PC
 
USB interface (All data can be downloaded using Download Manager (supplied) or Megger Powersuite Professional software. for Model MIT330
Test Result Storage 1000 results (last result may be recalled to the display). for Model MIT330
 
 
Resistance Ranges (Models MIT320, MIT330) can be used for Diode Testing
Measuring Range 10Ω to 1MΩ
Open Circuit Voltage 5V
Short Circuit Current 1.5mA
Accuracy (at 20°C) ±5% ±2 digits up to 100
 
 
Environmental Specifications
Operating Temperature -10°C to +60°C
Storage Temperature -25°C to +70°C
Operating Humidity 93% R.H. at +40°C maximum
EMC In accordance with IEC 61326-1
Weatherproof IP54
 
 
Safety
Meets the requirements of EN 61010-1 CAT III 600V, phase to earth
Terminal Fuse 500mA (fast blow) 600V, 32mm x 6mm, ceramic HBC 10kA minimum.
 
 
General Specifications
Power Supply (battery)

 
Eight x 1.5V Alkaline type 'AA' (LR6) batteries (battery condition is constantly shown on the display as a four-section bargraph)
(Rechargeable NiMH cells may be used)
Battery Life 5000 consecutive tests (5 seconds per test) on any test using 2Ah batteries
Dimensions (all models) 203mm (L) x 148mm (W) x 78mm (D)
Weight 980g approx.