Set
up, plug in, download, and analyze
Homes, offices, hospitals, and factories depend on electronic devices.
And electronic devices depend on good power quality. The Fluke VR101S is the perfect
system for catching sags, swells, transients, outages and frequency variations on line
voltage at receptacles, where the most sensitive loads are connected.
The
VR101S is a starter system that includes a compact VR101 event recorder, an optical
interface cable, and EventView software that turns your PC into a power quality reporting
tool. Additional VR101 event recorders can be purchased individually, so you can monitor
several voltage conditions at multiple locations at once.
Download
Data Sheet (PDF 94.8kBytes) |
Features
Setup event parameters |
 |
| To set up a VR101 event recorder, just enter the event capture
limit parameters on your PC and load them into the recorder. EventView software and the
optical interface cable make it easy. Then plug the recorder into the outlet you need to
test, and leave it there's no need to leave a computer hooked up. The compact
recorder stores any voltage event that goes outside your limits. The VR101 recorder can
store up to as many as 4000 events and a flashing LED tells you when events have been
captured |
|
| Analyze data on your PC |
 |
| To get data out of the recorder, hook it back up to your computer.
EventView software can download a complete history of the events that occurred while the
recorder was plugged into the receptacle. The software lets you build a detailed report of
sags, swells, transients, outages and frequency variations with time-stamps and durations. Your PC communicates to the VR101 through an optical interface cable.
This means the PC and VR101 are insulated from each other for safety. The event recorder
is self-powered by a 7-year lithium battery, so it is not affected by power outages. Each
VR101 Recorder has its own real-time clock for time-stamping voltage events and is
identified by a unique factory-assigned code. With their clocks and ID codes, multiple
recorders can be placed throughout a facility to give a complete picture of power quality
|
Technical Specifications
| Electrical
(voltage versions, plug style, and manual languages are determined by country) |
120V Version
Operating Range: 70V to 140V
Nominal Frequencies: 50 Hz or 60 Hz
Power Consumption: 2W
230V Version
Operating Range: 140V to 270V
Nominal Frequencies: 50 Hz or 60 Hz
Power Consumption: 3W
|
| Sags,
Swells and Outage Measurements |
120V Version
Hot-to-neutral
Range: 0 to 200V rms
Accuracy: ±2V rms
Resolution: 1V rms
Neutral-to-ground
Range: 3 to 200V rms
Accuracy: ±2V rms
Resolution: 1V rms
230V Version
Hot-to-neutral
Range: 0 to 270V rms
Accuracy: ±2V rms
Resolution: 2V rms
Neutral-to-ground
Range: 3 to 150V rms
Accuracy: ±1V rms
Resolution: 1V rms
|
Transient
Measurements
*Minimum pulse width: 1 s |
Hot-to-neutral
Range: 100 to 2500V peak
Accuracy: ±(10% reading +10V)
Resolution: 10V
Neutral-to-ground
Range: 50 to 2500V peak
Accuracy: ±(10% reading +10V)
Resolution: 10V
Phase angle
Range: 20º to 180º, 200º to 360º
Accuracy: ±1º
Resolution: 1º
|
| Frequency
Measurements |
Range: 45 to 65 Hz
Accuracy: ±0.1 Hz (3 cycles min)
Resolution: 0.1 Hz
|
Time
Measurements
Events < 1 second |
Hot-to-neutral
Accuracy: ±0.5 cycles
Resolution: 0.5 cycles
Neutral-to-ground
Accuracy: ±1 cycle
Resolution: 1 cycle
|
| Events
>= 1 second (time stamp) |
Accuracy: ±(2 sec/day + 8 sec)
Resolution: 8 sec |
General
Specifications
| Memory
size |
4000 events |
| Battery
type |
3.5V lithium (non-replaceable) |
| Battery
life |
7 years |
| Physical
size |
3.35 in x 2.65 in x 1.35 in
(85 mm x 68 mm x 35 mm) |
| Weight
|
4 oz (120g) |
| Warranty
|
1 year |
| Environmental
|
Operating temperature: -40 to 160 ºF (-40 to
70ºC)
Relative Humidity: 0 to 95% (non-condensing) |
| Safety
|
CSA Certification pending, CSA-NRTL (to UL 3111)
certification pending, Complies with requirements of EN61010-1:1993 |
| Computer
Hardware Requirements |
IBM PC or 100% compatible, with Windows®
3.1, Windows® NT or Windows® 95 installed
and operating, at least one free RS-232 serial port, a pointing device (recommended), 2 MB
hard drive space, 4 MB RAM (8 MB for Windows 95) |
|
For additional information or to order, call Rapid-Tech today
 |