Rapid-Tech Equipment Logo Combo Kit Power Quality Recorder Power Quality Analyzer Multifunction Digital Multimeter

Nationwide - Call 1800 358 531 

Yokogawa Test Instruments Logo

CL255
2000 Amp AC/DC Clamp-On Tester


CL225 2000 Amp AC/DC Clamp-On Tester
Safety Conformity

Features
 
  • AC/DC current measurements with current ranges up to 2000A.
  • AC/DC voltage and resistance measurements
  • True RMS display
  • DC output.
  • 55mm in diameter of measurable conductor.
  • Sleep Function
  • Data Hold Function
  • Approved for conformity to safety standards EN61010-1, EN61010-2-031, EN61010-2-032  (CAT III 600V, CAT II 1000V).

 

 

Specifications

Parameter

Reference

Accuracy

DC Current

400/2000A

1.5+2

AC Current

400A/2000A (150 to 1700A)

1.5+3 (50 to 60Hz)

400A/2000A (150 to 1700A)

3.0+4 (30 to 1kHz)

 

2000A (1701 to 2000A)

3.5+3 (50 to 60Hz)

DC Voltage

40/400/1000V

1.0+2

AC Voltage

40/400/750V

1.5+3 (50 to 60Hz)

40/400/750V

2.0+4 (30 to 1kHz)

Crest Factor

 

3 or less

Resistance
 

400Ω/4000Ω
 

1.5+2 Beeps at below 20Ω
(continuity check)

Frequency

10Hz to 3999Hz

1.5+5

Output
 

DC 400A (0 to 400mV)

±1.5% rdg ±3mV

DC 2000A (0 to 200mV)

±1.5% rdg ±3mV

AC 400A (0 to 400mV)

±1.5% rdg ±3mV (50 to 60Hz)

AC 2000A (15 to 175mV/
150 to1700A)

±3.0% rdg ±3mV (40 to 500Hz)
 

AC 2000A (170.1 to 200mV/ 1701 to2000A)

±3.5% rdg ±3mV (50 to 60Hz)
 

 

At 23°C ±5°C, 75% RH or less
Accuracy: ±(% rdg + dgt) = ±(% readout + value of least significant digit)

 

 

General Specifications

 

Parameter

Specification

Method of detection

True RMS

Display

LCD (Digital Display: 3999 counts)

Response Time

Approx 1 second (on DC current and Voltage ranges)

Approx 2 seconds (AC current/voltage and resistance ranges)

Range Switching

Auto-range

Data Hold

On all ranges (without peak hold)

Peak Hold

On Current/Voltage ranges

Ambient Temperature

0°C to 40°C

Relative Humidity

up to 40°C     RH 85%   (no condensation)

Influence of External Magnetic Field

4A or less at 400A/m

Influence of Conductor Position

±(1.5% rdg + 3dgt) or less

Safety Standard

EN61010-1, EN61010-2-031, EN61010-2-032

Circuit Voltage

1000Vrms or less

Withstanding Voltage

5.55kV AC for one minute

Power Supply

6F22 (006P) 9V x 1 or 6LR61 x 1

Battery Life

Approx. 15 hours (continuous)

Consumed Current

Approx 15mA

Sleep Function

Approx. 10 minutes after last switch operation.

Diameter of Measurable Conductor

55mm at maximum

Dimensions

105mm (W) x 250mm (H) x 49mm (D)

Weight

Approx. 540g

Accessories

User's manual (IM CL255), Test Lead (98011), Output Plug (98012), batteries and Carrying case (93034)

 


Fluke | Hart | Reed | Yokogawa | EuroSMC | Kyoritsu | Megger | | Tenmars | Tektronix | Amprobe | CIE | Silvertronic |
 Site Map | Search | About Us | Contact Us

 

Rapid-Tech Equipment
ABN 79 883 184 102
1300 Ferntree Gully Road. Scoresby. Victoria 3179
P.O. Box 4243 Knox City Centre. Victoria 3152

Phone: +61 3 9763 3299     Fax: +61 3 9753 2132