CW120 and CW121
Clamp-On Digital Power Meters |
|
|
|

|
Features
- Compact and light weight body with large back-lit LCD.
- Current clamps in a range of sizes (50 A, 200
A, 500 A, 700 A,
and 1000–3000 A current clamps).
- Support for large capacity ATA flash memory (equipped with
PC card slot).
- Data can be saved at from 1 second.
- Wiring error check function.
- Two or Three load system.
- Simultaneous measurement of multiple use possible by
external control terminal.
- The CW120 Series can be connected to a PC's
RS-232 port to analyze data.
- Parameters setting tool (Toolbox) is included
to set measurement conditions through a PC.
- Support for a variety of connection types and
CAT III 600V. The CW120 covers single-phase 2-wire to
three-phase 3-wire, single-phase 2-wire to three-phase 4-wire
and measurements possible on systems up to 495 V.
CW120 and CW140 Series Datasheet (PDF)
(documents are in
PDF format and will open in a new window) |
|
|
|
|
|
|
General Information |
|
Measurement Function |
V/A/Active power/Reactive power/Power
factor (lead lag) /Frequency/ Active electric energy/Regenerative
electric energy (only on data saving) |
|
Input Voltage |
150/300/450V Range (CAT III 600V) Max:
450V +10% |
|
Current |
5/10/20/50/100/200/500/1000/3000A
(dependant on clamp probe used) |
|
Wiring Method |
CW120: Single-phase 2-wire,
Single-phase 3-wire, 3-phase 3-wire, and |
|
|
Single-phase 2-wire 2-load system |
|
|
CW121: Single-phase 2-wire,
Single-phase 3-wire, 3-phase 3-wire, and |
|
|
3-phase 4-wire, Single-phase 2-wire 2
or 3-load system |
|
Accuracy |
1.2% (0.8% of reading + 0.4% range)
(dependant on clamp probe used) |
|
|
|
|
External Dimensions |
117mm (W) x 161mm (H) x 51mm (D) |
|
Weight |
Approx 600g |
|
Power |
100V to 240V AC (CAT II) |
|
|
|