Rapid-Tech Equipment Logo Combo Kit Power Quality Recorder Power Quality Analyzer Multifunction Digital Multimeter

Nationwide - Call 1800 358 531 

 Yokogawa Test Instruments Logo

CW120 and CW121 Clamp-On Digital Power Meters - Specifications

 

 

Specifications

Environmental Requirements

Indoor usage at an altitude of 2000 meters or less.

Operating Temperature/Humidity

0–50°C, 5–85% RH (no condensation).

Storage Temperature/Humidity

-20–60°C, 90% RH (no condensation).

Insulation Resistance 

500 V DC, 50 MΩ or greater
Between voltage input terminals and case.
Between voltage input terminals and current input terminals, communication terminals, and control I/O terminals.
Between power line and case.
Between power line and current input terminals, communication terminals, and control I/O terminals.

Insulation Withstand Voltage 

5550 V AC for one minute
Between voltage input terminals and case.

3250 V AC for one minute
Between voltage input terminals and current input terminals,
communication terminals, and control I/O terminals.

2300 V AC for one minute
Between power line and case.
Between power line and current input terminals, communication terminals, and control I/O terminals.

Power Supply

100–240 V AC ±10%, 50/60 Hz

Consumed Power

8 VA maximum.

External Magnetic Field Effects

Within accuracy levels at 400 A/m.

External Dimensions

117mm (W) x 161mm (H) x 51 mm (D)

Weight

0.6 kg

 

Terminals

Voltage Input

CW120: 3 terminals

Banana terminals (safety terminals)

CW121: 4 terminals

Banana terminals (safety terminals)

Current terminals (HL)

CW120: 2 pairs

Banana terminals (safety terminals)

CW121: 3 pairs

Banana terminals (safety terminals)

External control
 I/O terminals RS-485

3 terminals (H/L/H)
4 terminals (+/-/SG/TM)M3

Screwless terminals
Screw terminals

 

Connectors

RS-232: Mini DIN 8-pin
AC power supply: 2-pin

Voltage input probes:

3 for CW120, 4 for CW121

Safety Standard -Voltage input line:

Compliant with EN61010-1, EN61010-2-031
Overvoltage category III (Max. input voltage : 600 Vrms).

Safety Standard -Power line:

 

Compliant with EN61010-1, EN61010-2-031
Overvoltage category II (Max. input voltage : 264 Vrms)
Pollution degree 2

EMC Emission

Compliant with
EN55011, Group1, Class A; EN61326; EN61000-3-2; EN61000-3-3

EMC Immunity

Compliant with EN61326

 

Electrical  specifications:

Conforms to EIA RS-232 or EIA RS-485.

Synchronization system:

Start stop synchronization.

Baud rates:

1200, 2400, 4800, 9600, 19,200 bps.

PC Card Interface Slot:

PC card slot TYPE II.

Compatible card:

ATA flash memory card.

Function specifications:

Saving measurement data, saving and reading settings data.

Faulty Wiring Check details:

Presence/absence of power input; check for frequency measurement range; voltage phase sequence;
presence/absence of power input; whether current clamp is reverse-connected.

Scaling Function Settings ranges:

The VT ratio and CT ratio can be set.
VT ratio: 1–10,000
CT ratio: 1–10,000 (in increments of 0.01)

External Control I/O (RS-232 support only) (RS-485 not provided for)

Control input:
Control output:

 

TTL level or contact.
TTL level.
These input and output can be used as signals for starting and stopping integrating measurement.

Other Functions

Clock (typical precision:±100 ppm), key lock, system reset.
 

Saving Items:
 

Voltage, current, active power, reactive power, power factor, frequency, active electric energy, regenerative electric energy.

 

Display screen:

Backlit segmented LCD.

Electric energy:
Other parameters:

6 digits.
4 digits

 

Range Makeup: (rated values) Current Clamp-On Probe #96030

Voltage Wiring 20.00 A 50.00 A 100.0 A 200.0 A

150.0V

1ø2W 3.000 kW 7.500 kW 15.00 kW 30.00 kW
1ø3W

6.000 kW

15.00 kW

30.00 kW

60.00 kW

3ø3W 6.000 kW 15.00 kW 30.00 kW 60.00 kW
3ø4W 9.000 kW 22.50 kW 45.00 kW 90.00 kW

300.0V

1ø2W 6.000 kW 15.00 kW 30.00 kW 60.00 kW
1ø3W 12.00 kW 30.00 kW 60.00 kW 120.0 kW
3ø3W 12.00 kW 30.00 kW 60.00 kW 120.0 kW
3ø4W 18.00 kW 45.00 kW 90.00 kW 180.0 kW

450.0V

1ø2W

9.000 kW 22.50 kW 45.00 kW 90.00 kW

1ø3W

18.00 kW 45.00 kW 90.00 kW 180.0 kW

3ø3W

18.00 kW 45.00 kW 90.00 kW 180.0 kW

3ø4W

27.00 kW 67.50 kW 135.0 kW 270.0 kW
 

Range Makeup: (rated values) Current Clamp-On Probe #96031

Voltage

Wiring

50.00 A

100.0 A

200.0 A 500.0 A
150.0V 1ø2W 7.500 kW 15.00 kW 30.00 kW 75.00 kW
1ø3W 15.00 kW 30.00 kW 60.00 kW 150.0 kW
3ø3W 15.00 kW 30.00 kW 60.00 kW 150.0 kW
3ø4W 22.50 kW 45.00 kW 90.00 kW 225.0 kW
300.0V 1ø2W 15.00 kW 30.00 kW 60.00 kW 150.0 kW
1ø3W 30.00 kW 60.00 kW 120.0 kW 300.0 kW
3ø3W 30.00 kW 60.00 kW 120.0 kW 300.0 kW
3ø4W 45.00 kW 90.00 kW 180.0 kW 450.0 kW
450.0V 1ø2W 22.50 kW 45.00 kW 90.00 kW 225.0 kW
1ø3W 45.00 kW 90.00 kW 180.0 kW 450.0 kW
3ø3W 45.00 kW 90.00 kW 180.0 kW 450.0 kW
3ø4W 67.50 kW 135.0 kW 270.0 kW 675.0 kW
 

Range Makeup: (rated values) Current Clamp-On Probe #96032

Voltage Wiring 200.0 A 500.0 A 1.000 kA  
150.0V 1ø2W 30.00 kW 75.00 kW 150.0 kW  
1ø3W 60.00 kW 150.0 kW 300.0 kW  
3ø3W 60.00 kW 150.0 kW 300.0 kW  
3ø4W 90.00 kW 225.0 kW 450.0 kW  
300.0V 1ø2W 60.00 kW 150.0 kW 300.0 kW  
1ø3W 120.0 kW 300.0 kW 600.0 kW  
3ø3W 120.0 kW 300.0 kW 600.0 kW  
3ø4W 180.0 kW 450.0 kW 900.0 kW  
450.0V 1ø2W 90.00 kW 225.0 kW 450.0 kW  
1ø3W 180.0 kW 450.0 kW 900.0 kW  
3ø3W 180.0 kW 450.0 kW 900.0 kW  
3ø4W 270.0 kW 675.0 kW 1.350 MW  
 

Range Makeup: (rated values) Current Clamp-On Probe #96033

Voltage

Wiring

5000 A

10.00 A

20.00 A

50.00 A

150.0V

1ø2W 750.0 W 1.500 kW 3.000 kW 7.500 kW
1ø3W 1.500 kW 3.000 kW 6.000 kW 15.00 kW
3ø3W 1.500 kW 3.000 kW 6.000 kW 15.00 kW
3ø4W 2.250 kW 4.500 kW 9.000 kW 22.50 kW

300.0V

1ø2W 3.000 kW 6.000 kW 15.00 kW
1ø3W 3.000 kW 6.000 kW 12.00 kW 30.00 kW
3ø3W 3.000 kW 6.000 kW 12.00 kW 30.00 kW
3ø4W 4.500 kW 9.000 kW 18.00 kW 45.00 kW

450.0V

1ø2W 2.250 kW 4.500 kW 9.000 kW 22.50 kW
1ø3W 4.500 kW 9.000 kW 18.00 kW 45.00 kW
3ø3W 4.500 kW 9.000 kW 18.00 kW 45.00 kW
3ø4W 6.750 kW 13.50 kW 27.00 kW 67.50 kW

 


Fluke | Hart | Reed | Yokogawa | EuroSMC | Kyoritsu | Megger | | Tenmars | Tektronix | Amprobe | CIE | Silvertronic |
 Site Map | Search | About Us | Contact Us

 

Rapid-Tech Equipment
ABN 79 883 184 102
1300 Ferntree Gully Road. Scoresby. Victoria 3179
P.O. Box 4243 Knox City Centre. Victoria 3152

Phone: +61 3 9763 3299     Fax: +61 3 9753 2132