MV1000 and MV2000 Recorder
Functions Page 2.

 
Alarm Function

Alarms Settable per Channel

4

Alarm Types

High/low limit, delay high/low limit, difference high/low limit, high/low limit on rate of change.

Delay Alarm Time

Can be set according to channel (cannot be set according to level).
Range: 1 to 3600 seconds.

Time Intervals

(for the rate-of-change alarm)
A factor of 1 to 32 times the measurement interval (applies to all channels)

Display

When an alarm occurs, the state (the alarm type) or common alarm state appears on the digital display.

 
 
Event Action Function

Description

A set action occurs in response to a set event

 
 
Security Functions

Description

You can customize key lock security functions for any transmission or keyboard command.

Key Lock

Sets a password-protected key lock on all command keys and FUNC screen operations.

Login

Limits access to the MVAdvanced with a login that prompts for username and password.

Security Levels and User Numbers

System administrators: 5
General users: 30

 
 
Clock Functions

Clock

Comes with a calendar function (for western calendar)

Clock Accuracy

±10ppm (does not include the less than one second delay that occurs when turning the power on).

 
 
Communication Function

Electrical Specifications

IEEE 802.3 compliant (DIX frame)

Transmission Media

Ethernet (10Base-T)

Protocols Implemented

TCP, UDP, IP, ICMP, ARP, DHCP, HTTP, FTP, SMTP, SNTP, Modbus, and MV dedicated protocol.

E-mail Transmission (E-mail client)

Automatically sends an e-mail in response to alarms and other events.

FTP Client Functions

Automatically sends data files to an FTP server.
Transmittable files: Display data files, event data files, report data files, screen snapshot data files.

FTP Server Functions

Can transfer and delete files, manipulate directories, and produce file lists remotely from a network computer.

Web Server Function

Displays MV screen images on a web browser.

SNTP Client Function

Queries a specified SNTP server for the time and synchronizes with it.
Time query methods: Set interval, start of memory, sample, manual.

SNTP Server Function

Transmits the MV time settings via SNTP protocol.

DHCP Client Function

Automatically retrieves the network address settings from DHCP server.
Information retrieved automatically:
IP address, subnet mask, default gateway, DNS information.

Modbus Client Function

Loads data from other devices using Modbus protocol.*
*The calculation option (/M1) is required or the external input channel option (/MC1) is required to load data.

Modbus Server Function

Data can be read from MV using the Modbus protocol.

 
 
Batch Function

Description

Allows for data display, data management, text field functions, and batch comment input using batches.


Fluke | Hart | Reed | Yokogawa | EuroSMC | Kyoritsu | Megger | | Tenmars | Tektronix | Amprobe | CIE | Silvertronic |
 Site Map | Search | About Us | Contact Us

 

Rapid-Tech Equipment
ABN 79 883 184 102
1300 Ferntree Gully Road. Scoresby. Victoria 3179
P.O. Box 4243 Knox City Centre. Victoria 3152

Phone: +61 3 9763 3299     Fax: +61 3 9753 2132