MV1000 and MV2000 Recorder
Options |
|
| |
|
Alarm Output
|
|
Alarm Output Relays
Options (/A1,/A2, /A3, /A4) |
Activates the relay output on
the rear panel when an alarm occurs |
|
Alarm Output Points |
Choose from 2, 4, 6 or 12
(only with the MV2000 series)
(not installable on models MV1008 or MV1024) |
|
| |
| |
|
Serial
Communication |
|
Options (/C2, /C3) Media |
EIA RS-232 (/C2) and
RS-422/485 (four-wire) (/C3) compatible |
|
Protocols Implemented |
The dedicated protocol and the
Modbus (master/slave) protocol |
|
Settings/Measurement Server
Functions |
Using the dedicated protocol,
the following functions are available. |
|
Settings and commands
equivalent to the unit's key commands |
|
Data output |
|
Modbus master/slave
functions |
Loads data from other devices
using Modbus protocol. (the calculation option (/M1) or
the external input channel option (/MC1) is required to
load data). |
|
| |
| |
|
Fail/Status Output
Relay |
|
Option (/F1) |
Activates a relay output upon
the detection of a CPU abnormality on the MV or a set
condition. |
|
| |
| |
|
Calculation
Function |
|
Option (/M1) |
Performs calculations as well
as displays and records the trends or numeric values of
calculation channels listed below. |
|
| |
|
Maximum No. of
Calculation Channels |
Model MV1004 |
12 channels |
|
Model MV1006 |
24 channels |
|
Model MV1008 |
12 channels |
|
Model MV1012 |
24 channels |
|
Model MV1024 |
24 channels |
|
Model MV2008 |
12 channels |
|
Model MV2010 |
60 channels |
|
Model MV2020 |
60 channels |
|
Model MV2030 |
60 channels |
|
Model MV2040 |
60 channels |
|
Model MV2048 |
60 channels |
|
Maximum Equation Length |
120 characters |
|
Calculation Types |
General Calculations |
Basic arithmetic, square
root, absolute value, |
|
common logarithm, natural
logarithm, exponent, |
|
power, relational operations
(<, ≤, >, ≥, =, ≠), |
|
logical operations (AND, OR,
NOT, XOR) |
|
Statistical Calculations |
TLOG (maximum value, minimum
value, and P-P |
|
value for time series data) |
|
Special Calculations |
PRE, HOLD(a):b, RESET(a):b,
CARRY(a):b |
|
Conditional Statement |
[a?b:c] |
|
Max. Settable Constant |
60 (K01 to K60) |
|
Report Function |
Report Types |
Hourly, daily, hourly +
daily, daily + weekly, |
|
daily + monthly |
|
Calculation Types |
Reports can be calculated
using a combination of up to four of the following: |
|
Average, maximum value,
minimum value, |
|
integrated value, and
instantaneous value. |
|
| |
| |
|
RTD Input/3-wire
Isolated RTD Input |
|
Cu10/Cu25 RTD
input/3-wire Isolated RTD Input
Option (/N1) |
Enables the use of Cu10 and
Cu25 inputs in addition to the standard inputs.
|
|
| |
| |
|
3-Wire Isolated RTD
Input |
|
3-wire Isolated RTD Input
Option (/N2)
|
All RTD terminals (A, B, and
b) are isolated.
Note: Only available with Models MV1006, MV1012, MV2010,
MV2030, MV2040 and MV2048. |
|
| |
| |
|
|
|
External Input
Option (/N3)
|
Enables the use of the
following thermocouples and RTD's in addition to the
standard inputs. |
|
Thermocouples (TC) |
Kp vs Au7Fe, PLATINEL,
PR40-20, NiNiMo, W/Wre26, TypeN(AWG14). |
|
RTD's |
Pt25, Pt50, Ni100(SAMA),
Ni100(DIN), Ni120, J263*B, Cu53, Cu100. |
|
| |
| |
|
Remote Control |
|
Remote Control
Option (/R1) |
The MV models can be
controlled through contact input (up to eight (8)
inputs can be set). |
|
| |
| |
|
24V DC Transmitter
Power Supply |
|
|
24V DC Transmitter Power
Supply
Options (/TPS2*),
(/TPS4*)
|
Output Voltage |
22.8 to 25.2V DC (for rated
current load) |
|
Rated Output Current |
4 to 20mA DC |
|
Max. Output Current |
25mA DC (over-current
protection level: approximately 68mA DC). |
|
*/TPS2 |
is only available for MV1000
Series |
|
*/TPS4 |
is only available for MV2000
Series |
|
| |
| |
|
|
|
Pulse Input
Option (/PM1)
|
Contact and open-collector
pulse input is possible through the use of special
remote input terminals. The calculation (/M1) and remote
control (/R1) options are included in with the pulse
input option. |
|
Number of Inputs |
3 channels (however, if the
remote control input terminals are used for pulse input,
then up to 8 channels can be made available). |
|
Input Methods |
Photocoupler isolation (no
isolation between channels). Internal isolated power
supply (approx. 5V). |
|
Input Types |
Dry contact, open collector
(TTL or transistor) |
|
| |
| |
|
|
|
Input Value Correction
Option (/CC1) |
Ten-segment linearizer
approximation can be used on every measurement channel
to correct input values. |
|
Settable Points |
2 to 16 (settable
broken-line points) |
|
| |
| |
|
|
|
Channel Expansion
Option (/MC1*)
|
You can use the Modbus
master function to load data from other devices, and set
data through the use of communication input commands.
Additional channels are provided for communication
input. |
|
Note* |
This option only available
with Models MV2010, MV2020, MV2030, MV2040 and MV2048. |
|
Note 1 |
When equipped with external
input channel option, the High-Speed mode measurement
interval is unavailable. |
|
External Input Channels |
240 channels (channel
numbers 201 to 440) |
|
|